Hubbell Killark KFLX Series Installation, Operation & Maintenance Data Sheet Download Page 3

  

 

 

2112 Fenton Logistic Park Blvd.  
Fenton, MO 63026 USA 
P/N KIL00921505 FORM NO. K1505 ECO6-040-20 R04/20 

 

 

 

 

 

Page 3 of 4

 

 

 

 

 

 

 

 

Conditions for Safe Use: 

1. To prevent ignition of hazardous atmospheres, disconnect ballast/fixture from supply circuit before opening. keep tightly 
closed when in operation. 
2. Do not open, maintain or service in an area where an explosive atmosphere may be present. 
3. When Polycarbonate lens is in use, clean lens with damp cloth to avoid static discharge. 
4. the luminaire shall only be installed where there is a low risk of mechanical damage.  
 

Battery Backup Fixtures: 

IMPORTANT: To turn the fixture completely off, an un-switched AC power source of 120VAC to 277VAC is required for the 
yellow/black and white leads. If the yellow/black and white leads are attached to switched power, the fixture will go into battery 
backup mode if the switch is turned off. 

IMPORTANT: A switched or un-switched AC power source of 120VAC to 277VAC is acceptable for the black lead.  Fixtures with 
terminal blocks are shipped with a jumper between the terminals of the black and yellow/black wire.  Remove the wire link 
(jumper) and attach the yellow black wire to line voltage when local switching is required. 

The battery must be charged for at least 12 hours prior to testing.  

 

 
 
 
 

 

SELF DIAGNOSTIC INSTRUCTIONS / OPERATION: The self diagnostic feature is set from the factory. The 
emergency LED driver will conduct a self check for thirty (30) minutes every thirty (30) days; and ninety (90) minutes 
or one hundred eighty (180) minutes self check every 12 months. After every self check the LED indicator light will 
indicate a status signal. Dip Switch 1 Set to ON will run the emergency function at 10W for at least 90 minutes. Dip 
Switch 2 set to OFF will run the emergency function at 5W for 180 minutes. To disable this feature, set the Dip 
Switch 2 to the OFF position. 

 
 

 

 
 
 
 
 

The battery switch must be turned to the “ON” position for the fixture to operate correctly.     The fixture will not light up in 
battery backup mode until AC power is supplied once while the battery switch is in the “ON” position.  Thereafter, the 
fixture will operate in battery backup mode when the AC power is off. 

 

Battery Back-Up Connection with 

Terminal Block

 

 

AIMING DESIGNATIONS 

 

In environments with high dust, the dust will cover the lens and increase the temperature of the fixture. In a high dust 
environment use the aiming diagram shown below as directed on the nameplate. The angle shown below will keep dust from 
accumulating on the lens. 

 

Figure A                                                                                      Figure B 