H-MOSS

®

 Motion Switching System

Passive Infrared / Ultrasonic Occupancy Sensors

Installation and Operating Instructions

PD2611 

Page 1 

04/15 

FIGURE 1 
MULTI-TECH, DUAL

CIRCUIT, GROUND 

CONNECTION 

FIGURE 2
MULTI-TECH, SINGLE 

CIRCUIT, GROUND 

CONNECTION

FIGURE 3
ULTRASONIC, DUAL 

CIRCUIT, NEUTRAL 

CONNECTION

FIGURE 4
PASSIVE INFRARED, 

SINGLE CIRCUIT, NO 

BUTTON, NEUTRAL 

CONNECTION

COVER RELEASE

CATCH

LINE CIRCUIT

BLACK

PHOTOCELL

PUSH BUTTON

GROUND

CONNECTION

RED

BUTTON A

(TEST BUTTON)

BUTTON B

BLUE LOAD 2

LOAD 1

COVER RELEASE

CATCH

LINE CIRCUIT

BLACK

PHOTOCELL

PUSH BUTTON

GROUND

CONNECTION

RED

BUTTON A

(TEST BUTTON)

LOAD

LOAD 2

LOAD 1

COVER RELEASE

CATCH

LINE CIRCUIT

BLACK

PHOTOCELL

PUSH BUTTON

NEUTRAL 

WHITE

BUTTON A

(TEST BUTTON)

BUTTON B

BLUE

GROUND

CONNECTION

LOAD

COVER RELEASE

CATCH

PHOTOCELL

PUSH BUTTON

LINE CIRCUIT

BLACK

NEUTRAL 

WHITE

GROUND

CONNECTION

(TEST BUTTON 

LOCATED 

UNDER COVER)

WIRING DIAGRAMS

DESCRIPTION

The H-MOSS® sensor is an intelligent self-adapting occupancy 

sensor that is designed to replace existing wall switches.

SPECIFICATIONS

• 1000 sq. ft. coverage area (Models: AP and AD)

• 400 sq. ft. coverage area (Models: AU)

• Single or Dual Circuit 120/277VAC, 50/60Hz operation

• Electrical Ratings: (Each Output Separately)

  120VAC – 800W Incandescent, 1000W Ballast, 1/4 HP

  277 VAC – 1800W Ballast, 1/4 HP

• Adjustable Time Delay: 4-30 minutes, self-adapts based on 

  occupancy

• Light Level Adjustment (Circuit B output on Dual Circuit versions): 

 10 to 500FC

• UL, cUL Listed

PRECAUTIONS

CAUTION: RISK OF ELECTRICAL SHOCK. Turn power off at service 

panel before beginning installation. Never wire energized electrical 

components.

CAUTION: USE COPPER CONDUCTOR ONLY

Read and understand all instructions before beginning installation.

NOTICE: 

 For installation by a licensed electrician in accordance with 

National and/or local Electrical Codes and the following instructions.

NOTICE:

 For indoor use only.

Confirm device ratings are suitable for application prior to installation.  

Use of device in applications beyond its specified ratings or in

applications other than its intended use may cause an unsafe            con

-

dition and will void manufacturer’s warranty.   

NOTICE: 

 Do not install if product appears to be damaged.

NOTICE:

  Connect to field wiring rated for 60°C or greater.

INSTALLATION

1.Turn power OFF at the service panel.

2.Remove the old switch(es) if applicable.

3.Wire as shown in the 

WIRING DIAGRAMS 

section. Figures 1 and 2 

   denote wiring method for Leakage to Ground Sensors (

NOTE:

 A  

   secure ground is required for proper operation). Figures 3 and 4 

   denote wiring method for Neutral Wiring Sensors.

4.Install sensor in wall box using mounting screws provided.

5.Restore power to the sensor and allow it to initialize (up to 2 minutes).

6.Sensor is factory configured to provide the most energy savings. If 

   additional adjustments are required, see the 

ADJUSTMENTS

 

   section. 

7.If daylight harvesting is desired, calibrate the sensor’s photocell as

   described in the 

PHOTOCELL CONTROL

 section.

8.Install a decorator style wall plate (not included).

TEST MODE

1.Make sure lights are ON

2.Press and hold the ON/OFF button. Lights will cycle OFF then back

   ON. Release the ON/OFF button.

• For dual circuit sensors, press and hold the ON/OFF button for 

  Circuit A. 

• For sensors without buttons, remove the cover (see ADJUSTMENTS

  section) and  press and hold the Test Button.

3.Sensor is now in Test Mode (

NOTE:

 While in Test Mode the sensor

   will operate in Automatic ON/Automatic OFF mode). Vacate room; 

   lights should turn OFF after 5 seconds. Wait 5 seconds after turn

   OFF before re-entering space. Step back into room, lights will turn

   back ON. Repeat walk test as necessary to confirm sensor is 

   operating and detecting in the area as desired. Sensor will flash red

   and/or green LED while moving to indicate Passive Infrared (PIR) or

   Ultrasonic occupancy detection respectively. NOTE: Sensors with

   ultrasonic technology can be very sensitive and may require more

   than 5 seconds of no movement before turning lights off.

4.To exit Test Mode, press any button. 

NOTE: 

Sensor will automatically exit Test Mode after sixty (60)minutes.