Hubbell CHANCE M3 Installation, Operation And Maintenance Download Page 4

Part No. P807-0198

Rev.  B 6/96

MAINTENANCE

The Chance M3 disconnect switch should require
little maintenance.  Following a program of periodic
inspection and maintenance will prolong the life of
the M3 switch.

• Operate the switch periodically to clean contact

surfaces and to free moving parts.

• Check for burned or pitted contacts and replace if

necessary.

• Check hinge bolt for looseness, and if loose, torque

to 40-in.-lb. and apply Loctite®-271 to bolt threads.

• Inspect all blade rivets for tightness and replace

blade if loose.

• Inspect  mounting hardware and  tighten as

n e eded (12 - 15- ft.lb.)

• Replace any broken or cracked insulators and

clean or replace if heavily contaminated.

For additional recommendations, refer to ANSI
C37.35 “IEEE Guide for the Application, Installation,
Operation, and Maintenance of High Voltage Air
Disconnecting and Load Interrupter Switches.”

4

© Copyright 1996 Hubbell / Chance, 210 N. Allen, Centralia, MO  65240    Printed in USA

®

®