Hubbell CHANCE C4031762 Owner'S Manual Download Page 9

9

©2021 Hubbell Incorporated | Chance

®

 DC Hi-Pot Adapter Operating Instructions

Maintenance

Repairs

The CHANCE

®

 DC Hi-Pot Adapter is an electronic instrument and, if properly cared for, will 

provide many years of trouble-free service. Keep all parts clean and dry. 

Clean only with water 

or a mild soap & water solution. Do not use chemical solvents.

 When using soap for cleaning, 

it is required to thoroughly rinse all soap residue off the unit before placing back into service. 
Any remaining soap residue may allow high voltage tracking especially in the presence of high 
humidity and/or moisture. Do not use CHANCE

®

 Moisture Eater II wipes on any part of the DC 

Hi-Pot Adapter as it will cause damage.

We recommend that every Hi-Pot Adapter be wiped clean and visually inspected for defects 
daily and before each use. If any defect or contamination that could adversely affect the 
proper operation, accuracy or mechanical integrity of the tool is suspected, the Hi-Pot Adapter 
shall be removed from service. Before placing back into service, the meter should be properly 
repaired (if necessary), cleaned, inspected, and tested for full operation.

Do not engrave on stick or Hi-Pot Adapter.

 Abuse or misuse will damage the unit. Store in a 

dry location, do not drop, and protect from jostling or impacts during storage, carrying, or use. 
See page 10 "Specifications" for operating and storage temperatures and humidity ranges.

For Hubbell Power Systems authorized repair or factory calibration, please contact:

M.W. Bevins Co.
9903 E. 54th St.
Tulsa, OK 74146
(918) 627-1273
(918) 627-1294 (FAX)
www.bevinsco.com

Be careful when handling the Hi-Pot Adapter. Do not drop or scratch the tool.

!

 

CAUTION

A standard Volt-Ohm Meter (VOM) will show “open” (no continuity) when measuring in 
both directions across the DC Hi-Pot Adapter. This is due to the extremely high value (in 
MegOhms) of the actual Rectifier diodes that are used to provide a high peak inverse 
voltage (PIV) rating when exposed to High Voltage levels. It is recommended to confirm 
the proper operation of the DC Hi-Pot Adapter by using the method described on page 6.

 NOTICE

Summary of Contents for CHANCE C4031762

Page 1: ...uous product improvement Please visit hubbellpowersystems com to confirm current design specifications Revision D 09 21 Owner s Manual Model No C4031762 and C4031763 NOTICE Before operating a CHANCE D...

Page 2: ...edures techniques etc that if not followed carefully could RESULT IN DEATH A WARNING refers to operating procedures techniques etc that if not followed carefully could RESULT IN INJURIES OR DEATH A CA...

Page 3: ...test the unit on a known energized voltage source See page 6 for instructions to confirm proper operation Minimum Approach Distances MAD should be adhered to at all times For the latest information an...

Page 4: ...rating Instructions Components of the DC Hi Pot Adapter Sleeve Allows Phasing Set to be inserted Identification Decal Contains model number and voltage rating info Threaded Input Connector Male Thread...

Page 5: ...between the AC source and the isolated cable under test If the isolated cable under test is faulted it will not be able to hold a DC charge and the Phasing Set will show a voltage differential betwee...

Page 6: ...see a reading that appears to be approximately 1 2 of the Phase to Neutral voltage then the DC Hi Pot Adapter is working as designed If no voltage meter reading is seen during this test check connecti...

Page 7: ...iversal Hotsticks of appropriate length Utilizing the DC Hi Pot Adapter requires the cable under test to be disconnected at the elbows from all transformers and be properly isolated then discharged pr...

Page 8: ...source and the cable being tested Good Cable Indication If the cable is good the meter needle will rise as the cable charges and then the meter indication will drop back to near zero when a full char...

Page 9: ...ed the Hi Pot Adapter shall be removed from service Before placing back into service the meter should be properly repaired if necessary cleaned inspected and tested for full operation Do not engrave o...

Page 10: ...Hz C4031763 35 kV AC maximum Phase to Phase system voltage 50 60 Hz Operating temperature range 20 to 80 C 4 F to 176 F Operating humidity range 5 to 95 Rh Storage temperature 20 to 60 C 4 F to 140 F...

Page 11: ...__________________________________________________________ __________________________________________________________________________________ __________________________________________________________...

Page 12: ...erating Instructions Hubbell Power Systems Inc 210 N Allen St Centralia MO 65240 www hubbellpowersystems com TD09229E Rev D Hubbell has a policy of continuous product improvement Please visit hubbellp...

Reviews: