Page 19 of 20
P403-3222 Rev. K 4/18
Maximum Protective Ground Resistance
5
10
15
20
25
30
35
5K
10K
15K
20K
25K
30K
35K
Vman = 100 V. Max.
Resistance (milliohms)
Graph 2
This chart represents the maximum allowable resistance of the protective ground, based upon the constraint that the maximum
voltage drop across the man will never exceed 100 volts, at any fault current level. Equations 3 & 4 were used, the variable was
the fault current level.
Fault Current (Amps)