Remove four #8-32 pan head screws [1] from top corners of floor box assembly and retain.
Remove transition [2] and mounting plate [3] assemblies from box and retain.
Install leveling screws [4] as shown in FIGURE A.
Make conduit connections in accordance with application and applicable electric codes.
Wiring channel [5] can be positioned along either side of box. Reinstall mounting plate [3] aligning short leg with
wiring channel (SEE FIGURE B).
1.
2.
3.
4.
5.
BEFORE CONCRETE POUR, SEE FIGURES A, B, & C
CAUTION: RISK OF ELECTRICAL SHOCK. Disconnect power before installing or servicing.
NOTICE: For installation by a qualified electrician in accordance with all national and local electrical codes,
communications standards, the following instructions and any instructions included with individual devices.
NOTICE: Insure data/communications circuits are separated from lighting/power circuits in accordance with the NEC
and CE Code requirements.
Use with CFBS1R6CVRxx series round covers or CFBS1R6FFCVRxx series round furniture feed covers.
Orient cover support collar [9] as required by removing and reinstalling screws [10]. Lap joint in collar defines the
hinge location of the cover (SEE FIGURES E & F).
Install finished flooring to within 1/8 inch [3.2 mm] of cover support collar [9]. FOR CERAMIC TILE - DO NOT GROUT
BETWEEN THE SUPPORT COLLAR AND TILE.
Adjust height of cover support collar flush to just below the finished floor. Cover support collar is adjustable for
finished floors of 0 inches to .25 inches [0.0 - 6.4 mm] thick. Tighten mounting screws [10] to 10 - 15 lbs-in torque
[1.1 - 1.7 N m]. For thicker floor finishes use accessory collars (CFB6RCVRR series), sold separately.
Seal the gap around the cover support collar [9] with a continuous bead of electrical grade type RTV silicone sealant
(SEE FIGURE G).
Use the provided floor gasket or apply a 1/4 inch [6.3 mm] thick continuous bead of electrical grade type RTV silicone
sealant compound around the perimeter on the underside of the flange [11].
Attach flange [11] to the cover support collar [9] using #8-32 flat head screws [12] provided with the cover. Tighten
to 10 - 15 lbs-in torque [1.1 - 1.7 N m].
15.
16.
17.
18.
19.
20.
Wiring Device - Kellems
Hubbell Incorporated (Delaware)
40 Waterview Dr.
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
CFB2G25R/CFB2G25RCR 2 GANG RECESSED SHALLOW FLOOR BOX
FOR ROUND COVER Installation Instructions