background image

1/2" DIA. 

THRU HOLE

SUPPLIED NUT

SMALL

BUSHING

SUPPLIED TEST SWITCH/

INDICATOR LIGHT

TY-WRAP

SW INDICATOR

LARGE 

BUSHING

PLASTIC

TUBE

SW INDICATOR

PLASTIC

TUBE

LARGE

BUSHING

EM DRIVER

 SMALL

BUSHING

SW LEADS

TIE WRAP

7/8" DIA THRU

      HOLE

BALLAST

CHANNEL

 COVER

 FIXTURE

DIFFUSER 

    LENS

93071446

ILLUSTRATION 2

ILLUSTRATION 1

93071446

93071446

ILLUSTRATION 3

TY-WRAP

UL SWITCH

COVER

UL SWITCH

COVER

Mounting Height: This product meets or exceeds the NFPA  minimum light 
requirements with all loads, down to the smallest rated lamp load, at heights up 
to 25.8ft (7.8m). Many factors influence emergency illumination levels, such as the 
lamp load selected, luminare design, and environmental factors, therefore end use 
verification is necessary. For field installations,when the attached luminaire is mounted 
at heights greater then 25.8ft (7.8m), the level of illumination must be measured in the 
end application to ensure the requirements of NFPA 101 and local codes are satisfied.

WIRING

Step 5. 

Select correct wiring diagram to connect the emergency driver to the LED load, AC LED driver and Switch. Make sure all connections are in accordance with the 

National Electrical Code and any local regulations.

Step 6. 

Install in a visible location the labels “CAUTION” & “STATUS” (see illustration 4).

Step 7. 

After installation is complete, supply AC power to the emergency ballast and join the converter battery connector.

Step 8. 

At this point, power should be connected to both the AC driver and the emergency driver, and the charging indicator light should illuminate indicating the battery 

is charging.

Step 9. 

A short-term discharge test may be conducted after the emergency ballast has been charging for one hour.

Step 10. 

Charge for 24 hours before conducting a long-term discharge test. Refer to “Operation” section below

Note: Make sure the necessary branch circuit wiring is available. An unswitched source of power is required.

          The emergency ballast must be fed from the same branch circuit as the AC ballast.

EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT

TYPICAL SCHEMATICS ONLY. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS

 SWITCH

INDICATOR

"CAUTION"

LABEL

"STATUS"

 LABEL

LED MTG PLATE

(LENS NOT SHOWN)

MOUNT PLD7M UNIT

ON TOP OF LED FIXTURE

TYPICAL LED

LIGHTING FIXTURE

ILLUSTRATION 4

LL

PLD7M/M2

PLD7M/M2

LL

EMERGENCY BACK-UP & AC DRIVER

EMERGENCY BACK-UP ONLY

EMERGENCY BACK-UP & AC DRIVER

AND STEP DIMMING

LL

RED
RED

BLACK

VIOLET (+)
BROWN (-)

WHITE

WHT/BLK

BLUE

YEL/BLK

YELLOW

LED (+)

LED (-)

 PLD7M

/M2

EM LED 

DRIVER

LED LOAD

HOT

COMMON

VIOLET (+)
BROWN (-)

CONVERTER BATTERY CONN.

TEST SW/LED INDICATOR

CAP

GROUND WIRE

SCREW SEM

NUT KEP

GROUND WIRE INSTALLATION