1/2" DIA.
THRU HOLE
SUPPLIED NUT
SMALL
BUSHING
SUPPLIED TEST SWITCH/
INDICATOR LIGHT
TY-WRAP
SW INDICATOR
LARGE
BUSHING
PLASTIC
TUBE
SW INDICATOR
PLASTIC
TUBE
LARGE
BUSHING
EM DRIVER
SMALL
BUSHING
SW LEADS
TIE WRAP
7/8" DIA THRU
HOLE
BALLAST
CHANNEL
COVER
FIXTURE
DIFFUSER
LENS
93071446
ILLUSTRATION 2
ILLUSTRATION 1
93071446
93071446
ILLUSTRATION 3
TY-WRAP
UL SWITCH
COVER
UL SWITCH
COVER
Mounting Height: This product meets or exceeds the NFPA minimum light
requirements with all loads, down to the smallest rated lamp load, at heights up
to 25.8ft (7.8m). Many factors influence emergency illumination levels, such as the
lamp load selected, luminare design, and environmental factors, therefore end use
verification is necessary. For field installations,when the attached luminaire is mounted
at heights greater then 25.8ft (7.8m), the level of illumination must be measured in the
end application to ensure the requirements of NFPA 101 and local codes are satisfied.
WIRING
Step 5.
Select correct wiring diagram to connect the emergency driver to the LED load, AC LED driver and Switch. Make sure all connections are in accordance with the
National Electrical Code and any local regulations.
Step 6.
Install in a visible location the labels “CAUTION” & “STATUS” (see illustration 4).
Step 7.
After installation is complete, supply AC power to the emergency ballast and join the converter battery connector.
Step 8.
At this point, power should be connected to both the AC driver and the emergency driver, and the charging indicator light should illuminate indicating the battery
is charging.
Step 9.
A short-term discharge test may be conducted after the emergency ballast has been charging for one hour.
Step 10.
Charge for 24 hours before conducting a long-term discharge test. Refer to “Operation” section below
Note: Make sure the necessary branch circuit wiring is available. An unswitched source of power is required.
The emergency ballast must be fed from the same branch circuit as the AC ballast.
EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT
TYPICAL SCHEMATICS ONLY. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS
SWITCH
INDICATOR
"CAUTION"
LABEL
"STATUS"
LABEL
LED MTG PLATE
(LENS NOT SHOWN)
MOUNT PLD7M UNIT
ON TOP OF LED FIXTURE
TYPICAL LED
LIGHTING FIXTURE
ILLUSTRATION 4
LL
PLD7M/M2
PLD7M/M2
LL
EMERGENCY BACK-UP & AC DRIVER
EMERGENCY BACK-UP ONLY
EMERGENCY BACK-UP & AC DRIVER
AND STEP DIMMING
LL
RED
RED
BLACK
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
BLUE
YEL/BLK
YELLOW
LED (+)
LED (-)
PLD7M
/M2
EM LED
DRIVER
LED LOAD
HOT
COMMON
VIOLET (+)
BROWN (-)
CONVERTER BATTERY CONN.
TEST SW/LED INDICATOR
CAP
GROUND WIRE
SCREW SEM
NUT KEP
GROUND WIRE INSTALLATION