High Output Emergency Lighting Units

Installation Instructions

IMPORTANT SAFEGUARDS

Warning:

This product contains chemicals known to the state of California to cause cancer, birth defects and/or

other reproductive harm. Thoroughly wash hands after installing, handling, cleaning, or otherwise

touching this product.

When using electrical equipment, basic safety precautions 

should always be followed including the following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

1. Do not use outdoors.

2. Do not let power supply cords touch hot surfaces.
3. Do not mount near gas or electric heaters.
4. Equipment should be mounted in locations and at heights where it will not readily be

subjected to tampering by unauthorized personnel.

5. The use of accessory equipment not authorized by the manufacturer may cause an unsafe

condition.

Caution: 

Halogen cycle lamps are used in this equipment.  To avoid shattering: Do not
operate lamp in excess of rated voltage.  Protect lamp against abrasion and
scratches and against liquids when lamp is operating.  Dispose of lamp with care.

6. Do not use this equipment for other than its intended purpose.
7. Service of this equipment should be performed by qualified service personnel.

SAVE THESE INSTRUCTIONS

TROUBLE SHOOTING

AC-On Light does not illuminate

• Check AC wiring connections.

Emergency lamps do not work

• Battery is shipped disconnected.  Connect leads from

PC board to battery terminals and charge before testing.

• Make sure connections to charger board are properly 

seated.

• Check wiring connections.

MAINTENANCE

Units should be tested and maintained in accordance with
National Electrical Code and NFPA 101 Life Safety Code
requirements.  It is recommended that emergency lighting units
be tested for 30 seconds once a month and for 90 minutes
once a year.

RECYCLING INFORMATION

All thermoplastic parts are recyclable.
All cartons contain recycled materials.  
Please recycle.

NOTICE:

Units contain rechargeable batteries which must be
recycled or disposed of properly.

LAMP REPLACEMENT

CAUTION: 

Halogen lamps operate at high temperatures.

Allow defective lamp to cool completely before attempting
replacement.

1.

Remove unit cover/lens assembly.

2.

Pull defective lamp from socket.

3.

Plug replacement lamp into socket. 

CAUTION:

Do not touch replacement lamp glass

envelope with bare fingers as damage to the lamp will
result.  Follow directions supplied with replacement lamp.

4.

Reinstall unit cover/lens assembly and

test unit.

Hubbell Lighting, Inc. Life Safety Products 

!

www.dual-lite.com

701 Millennium Blvd. 

Greenville, SC 29607 

864-678-1000  

Fax: 864-678-1415

Copyright

©

Hubbell, Inc., All Rights Reserved - Specifications subject to change without notice.  Printed in U.S.A.

0603127 B  9/08

Halogen cycle lamps operate at high
temperatures.  Do not store or place
flammable materials near lamp.

Self-Testing/Self-Diagnostic Models

All models ordered with the Spectron self-testing/self-diagnostic
electronics system provide:

Visual indication of AC power status
Visual Indication of all self-diagnostic test cycles
Visual indication of unit malfunctions including:

• Battery fault
• Charger fault
• Transfer fault
• Lamp fault

Bi-Color Status Indicator LED

Self-testing/self-diagnostic model units are provided with a single, bi-
color LED which serves as a combination AC power, self-test and
service alert status indicator.  During normal operation, the green
status LED will be constantly illuminated, indicating the presence of
AC power.  During all automatic or manual self-test cycles, the green
Status LED will blink at a one cycle per second rate indicating "Test In
Progress".  If a fault condition is detected during any automatic or
manual self-test cycle, the Status Indicator will illuminate alternately
red and green until the end of the test cycle in a coded sequence to
indicate the type of detected malfunction. 

Under normal operating conditions, the unit's red LED Status Indicator
will remain off.  Following any test cycle in which a malfunction is
detected, the red Service Alert LED will blink in a coded sequence
indicating the type of malfunction as shown in the following table:

Service Alert Code

Description

One blink ON

/pause

Battery not connected  

Two blinks ON

/pause

Battery fault

Three blinks ON

/pause

Charger fault

Four blinks ON

/pause

Transfer circuit fault

Five blinks ON

/pause

Lamp failure

Six blinks ON

/pause

Lamp calibration error

(1)

Seven blinks ON

/pause

Lamp overload condition

(1) See “Calibrating the Lamp Load” at right.

Calibrating the Lamp Load

Check to assure that lamps are of correct voltage and wattage and
properly seated in the lamp sockets.  Press and HOLD the test switch.
The unit’s attached lamp load will illuminate and then turn off after
several seconds and re-illuminate several seconds later.  Release the
test switch.  The green status LED will be flashing at a slow rate to
indicate calibration cycle in process.  Upon completion of the
calibration cycle, the lamps will extinguish and the status LED will
illuminate in a steady green state indicating the unit is in ready stand-
by mode. 

Manual Test

Using the unit test switch, users can initiate different duration test
cycles based on the following table:

Initiating Action

Test Cycle

Press test switch 

once

1 minute

Press test switch 

twice

5 minute

Press test switch 

3 times

30 minute

Press test switch 

4 times

60 minute

Pressing test switch at any time after a test cycle has begun cancels
remainder of test and returns unit to normal operation.  The test switch
can also be used to manually silence the audible alarm option (see
below) by depressing the switch until an audible beep is sounded.

Audible Alarm

(Optional)

Self-testing/self-diagnostic model units ordered with the optional
audible alarm feature provide an audible alert upon detection of a fault
condition during any manual or automatic test cycle. The audible alarm
will sound once every hour until the fault is corrected or the alarm is
manually silenced.  Audible alarm will automatically re-enable after 24
hours if manually silenced.