III.Measurement Methods

1. Connect SF6 equipment

Connect the threaded end of the measuring pipe to the switch connector, tighten with

a wrench, and close the needle valve on the other end of the measuring pipe;

Then insert one end of the quick connector on the test pipe into the sampling port on

the purity meter;

Connect the exhaust pipe to the air outlet.

Finally, connect the switch connector to the measurement interface of the SF6

electrical equipment and tighten it with a wrench;

2.Check the power

This instrument is recommended to use AC power first.

When using DC power, please check the battery level displayed in the upper right

corner. If the power level is lower than about 20%, please turn off the battery and continue

to use it.

3.Start measuring

First fully open the needle valve on the measuring pipe of the instrument, then adjust

the flow with the flow valve on the panel, adjust the flow to about 0.2L / M, and start

measuring the purity of SF6.

Measure for 1 ~ 2 minutes, you can read or save after the data is stable.

4.Storing data

After the equipment measurement is completed, you can save the data in the

instrument and press the "OK" key to call up the operation menu. For details, see the next

section.

5.Measure other equipment

After a device measures, close the needle valve on the measuring pipe and the

regulating valve on the purity meter. Remove the adapter from the SF6 electrical

equipment. If you need to continue measuring other devices, follow the steps above to

continue measuring the next device.

6. End of measurement

Summary of Contents for HZSF-801

Page 1: ...HZSF 801 SF6 Purity Analyzer User Manual Huazheng Electric Manufacturing Baoding Co Ltd...

Page 2: ......

Page 3: ...ment Panel Description 2 III Measurement Methods 3 IV Menu Operation 4 V Matters Needing Attention 6 Note Please warm up for 2 minutes before starting the test When testing please slowly open the flow...

Page 4: ...design can store up to 100 sets of test data Clear display The LCD screen directly displays the purity value time and date battery power and other content RS232 interface It can be connected to a seri...

Page 5: ...bracket adjustment buttons on both sides at the same time to adjust the angle of the bracket 2 Rear panel 3 LCD screen Flowmeter LCD keyboard Air inlet Flow valve Charging Switch RS232 Air outlet AC2...

Page 6: ...ower than about 20 please turn off the battery and continue to use it 3 Start measuring First fully open the needle valve on the measuring pipe of the instrument then adjust the flow with the flow val...

Page 7: ...this menu you can number the device and save the record 2 Check the records You can view and print previously saved records 3 Delete records You can delete previously saved records 4 Change the time...

Page 8: ...Vad X XXX Val 00 0 Open the pressure reducing valve set the output flow of the cylinder to within 0 2MPA and then open the needle valve in an appropriate amount and then adjust the flow valve to 0 2LP...

Page 9: ...ect Set Time and press OK to enter the Set Time page The time value can be decreased or increased by the Up and Down keys and the Left and Right keys can go to the next or previous modification field...

Page 10: ...7 need to connect the power cord to the 220V socket There is no need to turn on the power switch The instrument will automatically charge The charging time generally takes more than 20 hours...

Reviews: