display whether it’s positive grounding or negative grounding; If it's ungrounded,

it displays 999.9KΩ.

3. Open up ground-fault locator, LCD will display related parameters. If the

battery voltage is under voltage, it means the instrument's battery has no power

and needs to charge. Connect the charger's AC220V power supply, insert the

charging plug into charging jacks, after 3 hours' chargement the lithium battery

can be used again. This instrument's power is supplied by lithium battery, the

voltage will gradually decline in the process of using. When the voltage gets

down to less than 10.8V, buzzer alarm will output all along, which means the

instrument can not work, at the moment, we need to charge the battery; at the

same time, the interface prompt that 'synchronizing signal is shaking hands'.

Place the transmitter's 'bus-bar/by-pass' switch on 'by-pass', the receiver shows

'Synchronizing signal shake hands successfully; Transmitter, receiver, please

keep current status'. Whichever reboot or change status will makes receiver get

close to transmitter (reset by-pass) so that synchronizing signal shake hands

again.

4. Use the detection probe of ground-fault locator to lock each by-pass of

DC system, the LCD will show the value of the resistance to ground of current

by-pass and we advise each loop should be detected for 2-3 times to get a stable

value.

5. When using the detection probe to seek by-pass ground-fault, you can

lock the two feeder lines (both positive and negative ones) at the same time, by

only once, you can detect if there is ground-fault on this by-pass. You can also

Summary of Contents for HZGZ-IV

Page 1: ...HZGZ IV Portable DC System Ground Fault Locator Split Type Instruction Manual...

Page 2: ...e and it offers an online performance The instrument has a characteristic of high detection sensitivity strong anti jamming capability small volume light weight and it s easy to use When seeking DC sy...

Page 3: ...sitions without installment power break or shake the insulation the result can be 100 percent accurate 6 You can realize automatic detection by just open and close the current clamp s jaw opening the...

Page 4: ...ance s detection accuracy error 10 power consumption less than 1W overall dimensions length width height 238 134 45 mm weight 1 5kg adaptive temperature 10 50 Part 4 Function instructions of different...

Page 5: ...Analyzer Power switch place the switch on ON connect working power supply power indicator light lights up Bus bar branch when place the switch on bus bar the instrument detect bus bar it will detect...

Page 6: ...mic display 2 Ground fault locator 1 Power key 2 Operating key up down left right ESC escape ENTER 3 The display color screen resolution 320 240 dynamicly display 3 Locator s menu introduction Main me...

Page 7: ...etic function Main menu Phonetic function Phonetic function Main switch on Boot phonetic on Synchronizing prompt on Battery under voltage Grounding alarm on Volume level 10 ESC ENTER 1 Main switch pho...

Page 8: ...put when grounding resistance less than alarm threshold off buzzer alarm output when battery voltage less than alarm threshold default on 6 Volume level from level 1to level 16 default level 10 3 Sync...

Page 9: ...the ENTER button to start the detection default auto detection 5 Display function Main menu Display function Display function Test data display off ESC ENTER Detection interface display Waveform inte...

Page 10: ...ve grounding resistance 999 9 K Negative grounding resistance 999 9 K The value of AC string current 000 V No grounding resistance The positive and negative grounding voltage is in the second bridge n...

Page 11: ...ocator 1 Common interface Ungrounded Grounding locating Grounding resistance 999 K Grounding direction no Alarm threshold 060 K Detection status complete Synchronizing signal shaking hands complete pl...

Page 12: ...w opening open Synchronizing signal shaking hands Receiver please reset by pass status Press ESC to return main menu 2 Waveform interface Ungrounded Ungrounded Grounding locating Detecting 999 K Thres...

Page 13: ...to the socket of analyzer clip the positive bus bar red crocodile clip of signal output line on the positive ground of current bus bar clip negative bus bar of signal output line black crocodile clip...

Page 14: ...ed to charge the battery at the same time the interface prompt that synchronizing signal is shaking hands Place the transmitter s bus bar by pass switch on by pass the receiver shows Synchronizing sig...

Page 15: ...robe and position indicator is 1 5m analyzer s output line is 2 3m The length of the cable can be added but you also need to add some special instructions Part 7 Attentions and tips during fault detec...

Page 16: ...A and B Part 8 Matters need attention 1 Before using this instrument please read our instructions carefully 2 When using this instrument if DC system bus bar already have insulation monitor you must...

Reviews: