3

3.2 After the power on, the LCD displays Test current 200A and Test times 10s.

3.3 You can press“RESET”key to select the test mode

3.4 You can press “TEST” key to start testing, and the LCD displays as shown in the

following figure.

The resistance of the switch is then displayed on the LCD. When the test time reaches

10s or 60s, the test is completed. The instrument automatically turns off the DC constant

current of 100A or 200A supply, and the LCD flashes to display the resistance value of the

switch.

3.5 After the LCD flicker shows for a period of time, the tester re-enters the mode of

operation selection state. At this point, press the print key to print the current data results.

3.6 After the test, turned off the power and remove the power line and test wires.

IV.Common Breakdowns and Methods

1.The fuse blow after pressing ‘TEST’

Constant - current power supply is fault.

2.Instrument displays

2.1 Current circuit impassable, check test line and clamp

2.2 The resistance of the test product is too large or the test wire is too fine to reach the

selected test current.

2.3 Constant - current power supply is fault

3. Instrument displays

The resistance of the test product is out of range.

No current

Out of range

Test current

200A

Test times

10s

Test current

200A

Test times

60s

Test current

100A

Test times

10s

Test current

100A

Test times

60s

Test current

200A

Test times

10s

Testing 2s