6
Operation and Maintenance
6.1 Routine Maintenance
6.2 Alarm Handling
6.3 Parts Replacement
6.1 Routine Maintenance
6.1.1 Daily Maintenance
Table 6-1 Daily maintenance
Maintenance
Item
Method
Expected Result
Troubleshooting
Check alarms.
On the ECC800-
Pro WebUI, choose
Home > Active
Alarms and Query
> Historical
Alarms.
No abnormal
record is found for
current and
historical alarms.
See the ECC800-
Pro documents.
Check the smart
cooling product
status.
On the ECC800-
Pro WebUI, choose
Monitoring >
Cooling.
● The smart
cooling product
is powered on.
● The current
temperature
ranges from
18°C to 27°C
and the
humidity ranges
from 20% to
80%.
See the smart
cooling product
documents.