4 Maintenance Guide
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
42
Procedure
Step 1
On the home screen, choose
Maint
>
Performance Maint
Figure 4-18
Performance maint screen
Step 2
Tap
Clear
of a specific performance parameter to clear its runtime.
----End
4.2.5 Calibrating a Sensor
Context
Calibrate a sensor if the displayed temperature or humidity on the sensor deviates from
the actual value. For example, if the return air temperature measured by other
temperature detection devices at the return air detection point is 20°C while the value
measured by the sensor is 22°C, the sensor has an error of 2°C, and the calibration value
should be set to –2°C.
To calibrate a sensor, log in as the
Admin
or
Engineer
user.
Procedure
Step 1
On the home screen, choose
Maint
>
Sensor Adjust
Figure 4-19
Sensor adjust screen