
Figure 3-39 Connecting the ground cable of the top air-flow cabinet
Step 3 Connect the power cable and signal cable of the top air-flow cabinet to the UPS.
NO TE
● For cable connections for a dual-cabinet UPS, the 400K-FM model is used as an
example.
● For cable connections for a four-cabinet UPS, the 800K-FM model is used as an example.
Power cable connection method: Pull out the power cable (04093521-07) from the
cable trough of top air-flow cabinet 1, bind the cable along the post of the top
air-flow cabinet, and connect the cable from the side beam of the UPS to the
small holes on the UPS output U and output N copper bars.
Signal cable connection method: Connect the signal cable (04093521-01) of the
top air-flow cabinet routed out from the fan transit unit to the J23 and J29 ports
on the UPS parallel board respectively.
●
400K-FM cabling mode
UPS5000 Top Air-flow Cabinet
User Manual
3 Product Installation
Issue 02 (2022-01-19)
Copyright © Huawei Technologies Co., Ltd.
32