3.2.3.10 Installing a Backfeed Protection Card
Prerequisites
The shunt release needs to match the circuit breaker, and the operating voltage range includes
the 53.5 V DC.
Procedure
Step 1
Remove the cover from the optional card subrack on the control module. Install a backfeed
protection card.
Figure 3-26
Backfeed protection card
Figure 3-27
Installation position
Step 2
Connect cables.