UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
8 Technical Specifications
Issue 02 (2017-02-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
251
UPS
Maintenance
bypass switch
Mains input
switch
Bypass input
switch
Output
switch
0K-SM
A/3P
UPS5000-E-20
0K-FM
690 V AC/400
A/3P/MCCB
690 V AC/400
A/3P/MCCB
690 V AC/400
A/3P/MCCB
690 V AC/400
A/3P/MCCB
UPS5000-E-30
0K-SM
1000 V AC/630
A/3P
N/A
N/A
N/A
UPS5000-E-30
0K-SMT
1000 V AC/630
A/3P
N/A
N/A
N/A
8.3 Environmental Specifications
Item
UPS5000-E-200K-SM/FM
UPS5000-E-300K-SM/SM
T
Operating
temperature
0–40°C
Storage temperature
–40°C to +70°C
Humidity
0%–95% RH (non-condensing)
Altitude
0–1000 m
When the altitude is greater than 1000 m but less than 4000 m, the
rated power should be derated. For details, see the IEC62040-3.
8.4 Safety Regulations and EMC
Item
UPS5000-E-200K-SM/FM
UPS5000-E-300K-SM/S
MT
Item
EN62040-1: 2013
IEC62040-1: 2013
YD/T2165-2010
EMC
EN62040-2
IEC62040-2
IEC61000-2-2
IEC61000-4-2
EN61000-4-6
EN61000-4-3