UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
3 Installation
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
44
Tools and Meters
8)
(M6/M8/M12/M16)
lists only the common tools for installation and cable connection. For more dedicated tools
required, see the corresponding component manuals. Prepare tools based on site requirements.
3.1.3 Power Cables
If UPSs are connected in parallel, input and output power cables for each UPS should have
the same length and specifications.
lists the recommended cross-sectional areas for power cables.
requirements for power cable connectors.
lists the recommended UPS input switch
configurations.
Table 3-3
Recommended cross-sectional areas for power cables
Item
360 kVA
400 kVA
440 kVA
480 kVA
Mains
input
Mains input current (A)
640
711
782
853
Recommended
cross-sectional
area (mm
2
)
L1
2 x (4 x 185)
2 x (4 x 240)
3 x (4 x 185)
3 x (4 x 240)
L2
L3
N
PE
185
240
240
240
Bypass
input
Bypass input current
(A)
547
608
669
729
Recommended
cross-sectional
area (mm
2
)
L1
2 x (4 x 185)
2 x (4 x 240)
3 x (4 x 185)
3 x (4 x 240)
L2
L3
N
PE
185
240
240
240
Output
Output current (A)
547
608
669
729