7.3 Environmental Specifications
Item
Specifications
Operating
temperature
0°C to 40°C
Storage
temperature
–40°C to +70°C
Humidity
0–95% RH (non-condensing)
Altitude
0–1000 m
When the altitude is higher than 1000 m, the power is
derated as described in IEC 62040-3. The upper limit of the
altitude is 4000 m.
7.4 Safety and EMC
Item
Specifications
Safety
regulations
CE
EN 62040-1
CB
IEC 62040-1
TLC
YD/T 2165-2010
EMC
Conducted emission
EN/IEC 62040-2
Radiated emission (RE)
EN/IEC 62040-2
Low-frequency signal
interference
IEC 61000-2-2
Electrostatic discharge
immunity
IEC 61000-4-2
Conducted susceptibility
EN/IEC 62040-2
EN/IEC 61000-4-6
Radiated susceptibility
EN/IEC 62040-2
EN/IEC 61000-4-3
Electrical fast transient
(EFT)
EN/IEC 62040-2
IEC 61000-4-4
Surge protection
EN/IEC 62040-2
IEC 61000-4-5
Power frequency magnetic
field
IEC 61000-4-8
UPS5000-E-(30 kVA–120 kVA)-FM
User Manual
7 Technical Specifications
Issue 03 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
121