TP48200A-D17A5-2 Telecom Power
User Manual
3 Components
Issue 04 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
26
Pin
Signal
Description
3
RX232
Receives data over RS232.
7
TX232
Transmits data over RS232.
6
PGND
Connects to the ground.
8
NA
–
3.6 UIM02C
Panel
The user interface module (UIM02C) supports eight dry contact outputs, nine dry contact
inputs (including six universal dry contact inputs, one smoke sensor input, one water sensor
input, and one door status sensor input), and four analog parameter inputs (including one
ambient temperature and humidity input, two ambient temperature inputs, and one battery
temperature input).
Figure 3-8 shows a UIM02C panel.
Figure 3-8
UIM02C panel
Ports
Table 3-8
UIM02C ports
Port Type
Silk Screen
Description
Sensor ports
TEM-HUM
Ambient temperature and humidity sensor
WATER
Water sensor
TEMP1
Ambient temperature sensor 1
TEMP2
Ambient temperature sensor 2
GATE
Door status sensor
SMOKE
Smoke sensor
BTEMP
Battery temperature sensor
Dry contact input ports
DIN1
NOTE