TP48120A-HD15A1, TP48120A-HD15A2,
TP48200A-HD15A1, and TP48200A-HD15A2 Telecom
Power
User Manual
3 Components
Issue 03 (2020-01-04)
Copyright © Huawei Technologies Co., Ltd.
30
(4) Cancel button
(5) Down button
(6) Enter button
(7) Up button
Table 3-3
Indicator description
Name
Color
Status
Description
Run indicator
Green
Off
The SMU06C is faulty or has no DC input.
Blinking at 0.5
Hz
The SMU06C is running properly and communicating
with the host properly.
Blinking at 4 Hz
The SMU06C is running properly but is not
communicating with the host properly.
Alarm indicator
Red
Off
No critical or major alarm is generated.
Steady on
A critical or major alarm is generated.
Table 3-4
Button description
Button
Name
Description
Up
Turns to the previous menu or sets parameter values.
When setting parameter values, you can hold down
to quickly adjust values.
Down
Turns to the next menu or sets parameter values.
When setting parameter values, you can hold down
to quickly adjust values.
Back
Returns to the previous menu without saving the settings.
Confirm
Enters the main menu from the standby screen.
Enters a submenu from the main menu.
Saves the menu settings.
NOTE
The LCD screen becomes dark if no button is pressed within 30 seconds.
You need to log in again if no button is pressed within 1 minute. The preset password is 000001.
When setting parameter values, you can hold down
or
to quickly adjust values.
The LCD screen luminance increases or decreases if you hold down
and
or
and
simultaneously for
more than 2 seconds.
The SMU is reset if you hold down
and
simultaneously for more than 10 seconds.