SmartLogger1000
User Manual
7 WebUI
Issue 12 (2019-01-15)
Copyright © Huawei Technologies Co., Ltd.
228
After setting
Remote directory
, you can create a subdirectory in the default data upload directory
(specified by the FTP server).
If
Data export
is set to
Enable
, you can set the SmartLogger to report data regularly or at a
specified time. If you set the SmartLogger to report data regularly, you can choose whether to report
all data or only the incremental data of a day each time.
In
FTP file format
,
Format 2
has two more information points than
Format 1
: E-Day (current-day
energy yield) and E-Total (total energy yield).
Format 3
has more information points than the other
two format files: multimeter, PID module, user-defined device, and SmartLogger data.
The displayed formats of the file name and time can be set in
File Name
and
Time format
.
Y
,
M
,
D
,
H
, and
m
represent the year, month, day, hour (24-hour system), and minute respectively.
Table 7-11
Troubleshooting
Error Code
Troubleshooting Suggestion Error Code
Troubleshooting Suggestion
0x1002
No FTP server address is
configured. Configure the
address correctly.
0x1003
1.
Check whether the DNS
server address is correct.
2.
Check whether the domain
name of the third-party FTP
server is correct.
0x1004
No TP user name is configured.
Configure the user name
correctly.
0x1005
No FTP user password.
Configure the user password
correctly.
0x3001
1.
Check whether the FTP
server address is correct.
2.
Check whether the
third-party FTP server is
working properly.
0x3002
1.
Check whether the user name
of the FTP server account is
correct.
2.
Check whether the user
password is correct.
0x3007
Check whether data is allowed
to be uploaded through a client
to the third-party FTP server.
0x3008
Check whether there is a
SmartLogger data upload
directory on the third-party FTP
server.
Other error codes
Provide SmartLogger run logs
and contact Huawei technical
support.
-
-
7.10.3.2 Setting Email Parameters
The SmartLogger can send emails to inform users of the energy yield, alarm, and equipment
status information of the PV plant system, helping users to know the running conditions of the
PV plant system in time.
When using this function, ensure that the SmartLogger can be connected to the configured
email server and that the Ethernet parameters and email parameters for the SmartLogger are
correctly set. Ensure that no password is set between the SmartLogger and the email server.
Because of permission restriction, log in as
Advanced User
. Choose
Settings
>
to
access the target page.