3.12.4.3 Connecting the Monitoring Network Cable
Connecting the RS485 Monitoring Network Cable (Modbus-RTU Protocol)
When monitoring smart cooling products over northbound RS485, the EMS needs
3 seconds to collect data from one smart cooling product. Therefore, the time
required for collecting data from N smart cooling products in a group is 3 x N. If
the data collection time is longer than the performance requirement, you can
divide the smart cooling products into several groups. For example, if the EMS
needs to finish data collection in 12 seconds, you are advised to group smart
cooling products by four and connect the COM port of the main control module of
the first smart cooling product in each group to the RS485 port of the EMS.
Step 1 Make the COM network cable by referring to
.
Figure 3-43 Pin sequence of network cable
NO TICE
Except for pins 4 and 5, the cable of other pins must be cut off to prevent
interference.
Step 2 Group smart cooling products for monitoring based on performance requirements
and connect the monitoring network cables.
●
If there is no teamwork control, connect the COM port on each smart cooling
product to the customer's monitoring system. After powering on the device,
set the "RS485 monitoring grouping" of the last smart cooling product to
"Enable". Setting path: Settings > Comm Settings > Modbus Settings.
●
In CAN networking and no grouping, connect the COM/FE port on the last
smart cooling product to the monitoring device, as shown in
.
After powering on the device, set the "RS485 monitoring grouping" of the last
smart cooling product to "Enable". Setting path: Settings > Comm Settings >
Modbus Settings.