The net height of the raised floor should be greater than 400 mm for downflow units; otherwise, the
fan lowering will be affected. The raised floor is optional for upflow units.
W indicates the distance between smart cooling products, and the minimum W is 600 mm.
L indicates the front maintenance distance, and the minimum L is 900 mm. If this requirement
cannot be met, the minimum L after front doors are removed can be 800 mm.
3.1.2 Tools
list the tools for installing the NetCol8000-C.
Add or delete tools as required.
Table 3-1
General tools
Name, Specifications, and Appearance
Adjustable wrench
(200 mm x 24 mm)
Phillips screwdriver
(M4/M6/M8)
Flat-head
screwdriver
(M3/M4)
Fixed wrench
(36#/75#)
Socket wrench (13
mm/15 mm)
Pipe wrench (18#)
Electrostatic
discharge (ESD)
gloves
Wire stripper
Needle-nose pliers
Diagonal pliers
Combination pliers
Torch
Measuring tape
Step ladder
Polyvinyl chloride
(PVC) insulation
tape
Claw hammer