NO TICE
Ensure that the indoor temperature is always above 4°C during the leakage test
with water; otherwise, the pipes may experience frost cracks. If the indoor
temperature is below 0°C, take anti-freezing measures for the pipes.
Procedure
Step 1 Manually open the chilled water valve (100%).
Figure 4-86 Opening the chilled water valve
Step 2 Open the main water inlet valve for the water-cooled module.
Step 3 Gradually open the cooling water side needle valve. Air and chilled water flow out
of the needle valve together.
Step 4 Adjust the air exhausting speed until no bubble flows out of the needle valve.
Step 5 Tighten the cooling water side needle valve.
Step 6 Inject water to 0.8 MPa, and preserve the pressure for 24 hours. Then connect a
pressure gauge to a needle valve on the pipeline to measure the pressure. If the
reading remains unchanged, the pipe is not leaking. You can perform the following
operations.
----End