Procedure
Step 1 Choose Settings > Alarm Settings > T/H Sensor on the home screen.
is displayed.
Figure 5-20 Setting alarm parameter 1
Step 2 Tap Delay following Return-air temp invalid.
Step 3 Set the value to 5 and tap
, as shown in
.
Figure 5-21 Setting alarm parameter 2
----End
5.5 Commissioning Guide
5.5.1 Entering Diagnostic Mode
Context
●
On the diagnostic mode screen, you can turn on or off components, and
control their output ratio.
●
If you need to manually turn on or off system components in diagnostic
mode, log in as the Admin or Engineer user. Ensure that the smart cooling
product is started before operation.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual