NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
87
Figure 4-14
Setting SNMP port
SNMP Port
is set to
161
by default.
Step 6
Tap
Next Page
.
Step 7
Set SNMP trap parameters.
1.
Tap
Add
under
SNMP Trap
.
2.
Set
Trap Address
as planned and
Trap Port
to the actual port number.
Trap Port
is set to null by default.
3.
Select the
SNMP Version
. If an SNMPv3 user is configured, it is recommended that
SNMP Version
be set to
SNMPv3
.
4.
If
SNMP Version
is set to
SNMPv3
, select an
SNMPv3 user name
, and then tap
as shown in
Figure 4-15
Setting SNMP trap parameters
5.
Tap
Submit
under
SNMP Trap
.
----End