NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
7 FAQ
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
176
The temperature and humidity curves show the current average temperature and humidity of the
control type.
You can tap
and
to zoom in or out the range of the temperature and humidity ordinate.
The midpoint temperature is the temperature set point and the midpoint humidity is the humidity set
point after the ordinate range is zoomed in or out.
You can view the temperatures from (temp set point – 3°C) to (temp set point + 3°C) at least and
from (temp set point – 30°C) to (temp set point + 30°C) at most.
You can view the humidity from (humidity set point – 5%) to (humidity set point + 5%) at least, and
from (humidity set point – 50%) to (humidity set point + 50%) at most. Specific humidity
fluctuation range displayed varies according to different models of smart cooling products.
----End
7.1.2 Querying Logs
Context
The
Query Logs
screen displays the operations performed by the user.
Procedure
Step 1
On the home screen, choose
Maint
>
Query Logs.
Figure 7-2
Query logs screen
----End
7.1.3 Querying Component Status
Context
You can query component status in the following two ways.
Enter the
Status Summary
screen. The control or running status of major components
such as the chilled water valve, indoor fan are displayed.
Enter the
Device Details
screen and then enter the menu of a specific component. All
parameters for the component are displayed.