NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
164
Exercise caution because the device is still energized after it is shut down on the LCD.
Step 2
Open the rear door and remove the air filter.
Step 3
Use a Phillips screwdriver to remove the R-shaped pipe clip that secures the return air
temperature sensor on the side door support, as shown in
Figure 6-7
Position of the return air temperature sensor
Step 4
Remove the waterproof connector from the temperature sensor cable and remove the return
air temperature sensor probe.
Step 5
Secure the new return air temperature sensor to the original position using the R-shaped pipe
clip.
Step 6
Reconnect the waterproof connector to the sensor cable.
Step 7
Install the air filter. Close and lock the rear door.
----End
6.4.9 Replacing the Supply Air Temperature Sensor
Prerequisites
The supply air temperature sensor needs to be replaced.
A spare temperature sensor of the same model is available and functional.
Context
Temperature sensors can be replaced with power-on.
Recommended tools: diagonal pliers, cable tie, Phillips screwdriver
Preparation: Maintain from the front door.