Figure 4-13 Outdoor unit mounting holes
Table 4-3 Port dimensions (unit: mm)
Model
W1
W2
D1
D2
NetCol500-A060
1047
1181
924
1058
NetCol500-A080
1877
2011
924
1058
NetCol500-A120
1047
1181
2018
2152
Concrete Platform Requirements for Vertical Installation
For details about how to make concrete platforms to vertically install an outdoor
unit, see
. An outdoor unit must be fixed to a concrete platform or a
base using four M8x80 stainless expansion bolts and bracket angles.