NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
181
Table 6-6
Troubleshooting
Symptom
Possible Cause
Solution
The unit generates abnormal
voice.
Compressor, fans, or pipes
are loose.
Check the fixing structure
and ensure that all
components are securely
installed.
A compressor does not
work.
The high-pressure switch
reacts.
Check the high-pressure
switch status.
Circuit breakers, fuses, or
cables are disconnected.
Check the main circuit
breaker, compressor circuit
breakers, fuses, and cables.
A compressor motor is
damaged.
Replace the motor.
A compressor does not need
to start.
Check for any startup
requirement on the LCD.
The compressor driver is
faulty.
Check whether the driver is
faulty. Replace it if it is
faulty.
The compressor discharge
temperature is too high
The refrigerant loop or
component is blocked.
Clean up foreign matter
from the refrigerant loop.
The outdoor unit is installed
in an inappropriate position.
(The outdoor unit should not
be exposed to direct sunlight
and must be installed at a
specified spacing according
to the installation guide.)
Install the outdoor unit in a
correct position, without
exposure to direct sunlight
and with an appropriate
spacing.
Air exists in the cooling
system.
Exhaust air, and examine
and repair the pipeline.
Heat dissipation is poor
because of blockages in the
condenser.
Clean the condenser fins.
An outdoor fan fails.
Check whether the outdoor
fan works.
The refrigerant is
insufficient.
Fill more refrigerant.
The compressor discharge
pressure is too low.
The refrigerant is
insufficient.
Fill more refrigerant.
The outdoor fan speed
controller fails.
Replace the fan speed
controller.
The refrigerant leaks.
Check the pipeline for
leakages.