6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
180
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Causes
Solution
alarm
generated.
preheating the
compressor oil.
preheating in the Setting
menu.
a186
EEV driver
fault lock
Critical
The alarm is
generated.
The a142 EEV
driver fault alarm
is generated
frequently.
Refer to the solutions for the
a142 EEV driver fault alarm.
a189
Transformer
overtemperature
Critical
The alarm is
generated, and
the system
shuts down.
1.
Transformer
fault.
2.
A phase of the
power supply is
open.
1.
Replace the transformer.
2.
Check the power supply.
a190
Outdoor fan
driver fault lock
Critical
The alarm is
generated, and
the compressor
is forcibly shut
down.
Multiple outdoor
unit alarms have
been generated.
Check the outdoor unit alarms
and troubleshoot according to
the suggestions.
a191
EEV driver
power off
Critical
The alarm is
generated, and
the compressor
is forcibly shut
down.
EEV driver board
fault.
Replace the main control
module.
a192
Power phase B
open locked
Critical
The alarm is
generated, and
the system
shuts down.
1.
The power
grid is unstable.
2.
The phase B
cable is faulty.
1.
Check the power grid.
2.
Check the phase B cable is
faulty.
6.4 Troubleshooting
Certain circuits in the unit have lethal voltage. Only professional technicians are allowed
to perform maintenance.
Exercise caution during live-line troubleshooting.
If jumpers are used for troubleshooting, remove them after troubleshooting. Connected
jumpers may affect control functions and damage equipment.
describes how to troubleshoot the unit.