NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
162
Figure 5-7
Performance maintenance
Step 6
Tap
Startup
on the home screen. Ensure that the air conditioner is running normally without
any alarms.
----End
5.4.3 Replacing the Differential Pressure Switch
Prerequisites
The differential pressure switch needs to be replaced.
A spare differential pressure switch of the same model is available and functional.
Tool: Phillips screwdriver
Context
The differential pressure switch can be maintained only from the rear door.
Procedure
Step 1
On the controller home screen, tap
Shutdown
, and turn off the air conditioner switch in the
PDC.
Exercise caution because the device is still energized after it is shut down on the controller
home screen.
Step 2
Open the rear door and remove the air filter.
Step 3
Remove the pressure inlet tube, as shown by (1) in