NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
131
Figure 5-1
Removing a water pan filter
5.1.3 Quarterly Maintenance
lists quarterly maintenance items for the indoor unit.
Table 5-3
Quarterly maintenance checklist
Compone
nt
Item (Monthly
Maintenance)
Troubleshooting
Monitoring
Export air conditioner logs,
alarms, temperature, and
humidity, as well as the
operating status and time of the
compressor, fan, electric
heater, electric humidifier, and
water pump from the
monitoring system. View the
historical alarms generated in
this quarter and select the most
common five ones. (If no
monitoring system is available,
skip this item.)
Rectify the fault or contact Huawei
technical support.
Wet film
humidifier
Start the indoor unit. Choose
Maint
>
Diagnostic Mode
>
Enter
on the main screen, and
set the humidifier to a certain
value.
If no water is supplied, check the cable
connection or replace the water inlet
solenoid valve.
If no water is supplied to the wet film
humidifier, check the cable connection
to the water pump or replace the
humidifier pump.