If yes, the check is complete.
–
If no, check the cable connection and the settings of teamwork control
parameters.
4.5.2.7 (Optional) Setting Alarm Parameters
Prerequisites
Before setting the alarm parameters, get familiar with the relationship among
each parameter.
Configurations of temperature and humidity alarms and main board alarms for
the air cooled devices comply with the following relationships:
●
Power underfreq alarm threshold < Power overfreq alarm threshold
●
Supply-air HT alarm thr 5°C ≤ Return-air HT alarm threshold
●
Supply-air HT alarm thr 5°C ≤ Hot aisle HT alarm threshold
●
Cold aisle HT alarm thr 5°C ≤ Hot aisle HT alarm threshold
●
Cold aisle HT alarm thr 5°C ≤ Return-air HT alarm threshold
●
Supply-air LT alarm thr 5°C ≤ Return-air LT alarm threshold
Configurations of temperature and humidity alarms and main board alarms for
the chilled water devices comply with the following relationships:
●
Power underfreq alarm threshold < Power overfreq alarm threshold
●
Supply-air HT alarm thr 5°C ≤ Return-air HT alarm threshold
●
Supply-air HT alarm thr 5°C ≤ Hot aisle HT alarm threshold
●
Cold aisle HT alarm thr 5°C ≤ Hot aisle HT alarm threshold
●
Cold aisle HT alarm thr 5°C ≤ Return-air HT alarm threshold
●
Supply-air LT alarm thr 5°C ≤ Return-air LT alarm threshold
●
Supply-air LT alarm thr 5°C ≤ Hot aisle LT alarm threshold
●
Cold aisle LT alarm thr 5°C ≤ Hot aisle LT alarm threshold
●
Cold aisle LT alarm thr 5°C ≤ Return-air LT alarm threshold
Context
●
The content described in this section is optional. To set whether to report an
alarm, or set the time delay duration or threshold, follow the instructions in
this section. The enabling functions include the following three choices:
–
Allow
Alarms are reported to the EMS. Active alarms are displayed on the LCD
and the system performs related protection actions.
–
Block
New alarms are not reported to the EMS. The EMS can detect alarms that
are generated before the blocking. Active alarms are displayed on the
LCD and the system performs related protection actions.
–
Disallow
Alarms are not generated and no protection actions are performed.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
4 ACC Introduction
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
105