iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
185
If the network security certificate is encrypted, click
Browse
behind
Select a security
certificate
. Then select
Enable key password
, enter
Key password
, and enter
Confirm key
password
.
2.
For details about how to replace the security certificate for the NetEco, see the
Replacing a Security Certificate for Connection between NetEco and NE
chapter in
the NetEco user manual.
----End
6.4.1.3 Setting SNMP Parameters for the ECC500 V6 Collector
You need to set the SNMP parameters for the ECC500 V6 collector if it connects to the EMS,
as these parameters are needed for setting up the ECC500 V6 collector on the EMS.
Prerequisites
You have obtained the IP address, login user name, and password for the ECC500 V6
collector.
A PC with an IP address in the same network segment as the ECC500 V6 collector is
prepared, and the PC has been connected to the ECC500 V6 collector over a switch.
Procedure
Step 1
Log in to the WebUI of the ECC500 V6 collector.
Step 2
Choose
System Settings
>
SNMP Settings
.
Step 3
Select
SNMPv3
as
SNMP Version
, enter
161
for
SNMP Port Number
, as shown in
Figure 6-45
Setting SNMPv3 parameters (01)
Step 4
Click
Add
in
SNMPv3
, as shown in