iManager NetEco 6000
Device Installation and Commissioning Guide
4 Connecting Monitoring Cables to Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
116
Figure 4-59
PDU2000 ports
Step 2
Connect the other end of the network cable to the COM port on the ECC500 collector.
Step 3
(Optional) If multiple PDU2000s need to be cascaded, connect the COM1 port of one
PDU2000 to the COM2 port on the next PDU2000.
A maximum of four PDU2000s can be cascaded.
----End
4.3.8.3 Connecting a Monitoring Cable to an HPXPDU2000-16-3PH-24-6-M1
Prerequisites
A network cable used for monitoring is prepared.
Procedure
Step 1
Connect the monitoring cable.
1.
Connect one end of the network cable to port COM1 or COM2 on the PDU2000.