IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
10 Cable Layout
Issue 02 (2015-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
249
Figure 10-74
Wiring terminals on the TU520A ATS
Step 2
Connect the cord end terminal of the RS485 monitoring cable to the RS485 port in the
PDU8000.
lists the mapping between the wiring terminals in the RS485 port and
the colors of core wires in the cord end terminal.
Table 10-77
Mapping between the wiring terminals in the RS485 port and the colors of core wires
in the cord end terminal
Type of the Collector
Connected
Wiring Terminal in the
RS485 Port
Color of Core Wire in the
Cord End Terminal
CCU collector
16
Orange and white, blue
17
Orange, blue and white
ECC collector
16
Orange and white
17
Orange
Step 3
Connect the RJ45 connector of the RS485 monitoring cable to the RS485 port on the CCU
collector or ECC collector.
----End
10.12.48 Connecting a Monitoring Cable to a
PDU8000-0250ACV4-SCA005
Prerequisites
A network cable used for monitoring has been prepared.