6 Troubleshooting
Issue 01 (2014-3-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
40
If no, go to
Step 3
Check the connection between the gas release indicator and the controller.
Use a multimeter to check whether there is any short circuit or open circuit.
Y => Rectify the connection fault.
Check whether the fault is rectified.
If yes, no further action is required.
If no, contact Huawei technical support.
N => Contact Huawei technical support.
----End
6.4 Audible and Visual Alarm Fault
Possible Causes
The power supply to the audible and visual alarm is abnormal.
The audible and visual alarm is faulty.
The cable connection of the audible and visual alarm is abnormal.
Tools and Materials
Multimeter
Screwdriver
Step ladder
Procedure
Step 1
Check the power supply to the audible and visual alarm.
Trigger a smoke alarm and a temperature alarm when the cable is removed from the solenoid
valve, and observe whether audible and visual alarms are generated. Use a multimeter to
measure the DC24V+ and GND terminals of the audible and visual alarm, and check whether
the voltage is within normal range.
Y => Go to
N => Regulate the voltage to a normal value.
Check whether the fault is rectified.
If yes, no further action is required.
If no, go to
Step 2
Replace the audible and visual alarm.
Check whether the fault is rectified.
If yes, no further action is required.
If no, go to