IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
5 Parts Replacement
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
94
Step 4
Check that the new T/H sensor is working properly.
If the T/H sensor displays the temperature and humidity properly after power-on, the T/H sensor is
working properly.
----End
Follow-up Procedure
Dispose of the removed T/H sensor that is confirmed faulty.
5.3.2 Replacing a Water Sensor (Point Type)
Prerequisites
A water sensor needs to be replaced.
Spare water sensors of the same model are available and functional.
Impact on the System
None
Preparations
Tools: Phillips screwdriver, protective gloves
Material: spare water sensor
Document required: monitoring device layout diagram
Skill requirement: weak-current engineer
For the diagram and table, see the initial configuration guide.
Procedure
Step 1
Locate the water sensor to be replaced based on the alarm information on the monitoring
software terminal.
shows a point-type water sensor.
Figure 5-13
Point-type water sensor
Step 2
Remove the locking bolts of the water sensor using a Phillips screwdriver, and remove the
water sensor, as shown in