FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
4 Hardware Installation Preparations
Issue 01 (2019-03-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
42
Table 4-4
Required cables and circuit breakers
Name
Specifications
Quantit
y
Remarks
Power
cable
NetCol
5000-
C030H
6
NetCol
5000-
C030H
7
without
heating
and
humidif
ication
Power cable, 450 V/750 V,
H07RN-F, 2.5 mm
2
, black (3-core
cable colors: blue, brown, and
yellow-green)
2 PCS
Optional;
same cable
parameters
for the active
and standby
routes
2.5 mm
2
cord end terminal
4 PCS
Standard
configuratio
n; delivered
with the
product
OT terminal: M4x2.5 mm
2
2 PCS
Standard
configuratio
n; delivered
with the
product
NetCol500
0-C030H7
with
heating
and
humidificat
ion
Common power cable: power
cable, 300 V/500 V, 3x6.0
mm
2
, black (3-core cable
colors: blue, brown, and
yellow-green)
Backup power cable: power
cable, 300 V/500 V, 3x2.5
mm
2
, black (3-core cable
colors: blue, brown, and
yellow-green)
2 PCS
Optional
Cord end terminal of the
common power cable: 6.0 mm
2
Cord end terminal of the
backup power cable: 2.5 mm
2
4 PCS
Standard
configuratio
n; delivered
with the
product
OT terminal of the common
power cable: M4x6.0 mm
2
OT terminal of the backup
power cable: M4x2.5 mm
2
2 PCS
Standard
configuratio
n; delivered
with the
product
Remote shutdown cable
Power cable, 300 V/500 V,
60227IEC53(RVV), 0.75 mm
2
,
black (core cables: brown and
blue), 7 A
1 PCS
Engineering
purchasing
Bare crimp terminal, single cord-
end terminal, 1 mm
2
, 5 A, tin
plated, 6 mm insertion depth
2 PCS
Standard
configuratio
n; delivered
with the
product