FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
8 (Optional) Installing Cable Troughs
Issue 01 (2019-03-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
107
Figure 8-4
Rotating the vertical plate by 90 degrees
Step 3
Install the other vertical plate into the mounting hole in the second row counting from the
front door to the rear door in the same way. Install one M5x10 tapping screw inside each of
the two vertical plates to ensure equipotential bonding with the cabinet, as shown in
Figure 8-5
Installing the other vertical plate
Step 4
Press a supporting plate along the two vertical plates down to the place between the four
clasps and the cable bridge, as shown in
. Ensure that the supporting plate is fully
into the clasps.
When installing the supporting plate, do not remove the grommet strip on the U-shaped trough.