FusionModule5000 Smart Modular Data Center
Commissioning Guide
6 Commissioning the Management System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
93
After the first login, change the password in time to ensure account security and prevent unauthorized
network attacks, such as data tampering. Huawei will not be liable for any security issues caused by your
failure to change the preset password in time or password loss after changing.
3.
Choose
Local Configuration
>
Server configuration
. Set the service IP address
(internal IP address of the VCN), NAT IP address (external IP address of the VCN), time
zone, and time according to the site requirements.
Figure 6-35
Configuring the server
Set
Business IP
to XXX.XXX.XXX.XXX,
Subnet mask
to 255.255.254.0,
Gateway IP
to
XXX.XXX.XXX.XXX. The values here are examples. The actual values prevail.
Set
NAT IP
to
VCN external IP address
, which is the same as the external IP address mapped from
the VCN internal IP address displayed on the ECC800.
4.
Configure the NTP synchronization. After setting
The NTP clock source server
to
Yes
,
set the IP address of the NTP server.
The server that connects to cameras needs to enable the camera NTP synchronization function. For the
detailed operations, see
Step 2
Enabling camera NTP synchronization.
The camera NTP synchronization function for the server is disabled by default. The camera
NTP synchronization function needs to be enabled for the server that connects to cameras.
After the camera NTP synchronization function is enabled, cameras will automatically
time-synchronize from their access servers.
1.
Log in to the OMU portal of the VCN as the Admin user.
2.
Choose
Maintenance
>
Unified Configuration
.
3.
Select the server that the camera needs to access, set
Module name
to
SCU
and
Parameter type
to
System property
, and click
Search
.