7 Temperature Control System
Issue 06 (2020-05-21)
Copyright © Huawei Technologies Co., Ltd.
133
Item
Specifications
Expansion bolt hole
M12x60
Storage temperature
–40°C to +70°C
Storage humidity
5%–95% RH (non-condensing)
Maximum operating pressure
4.35 MPa
7.5.4 (Optional) Sunshade
When an outdoor unit is used in the T3 working condition (–5°C to +55°C), install a sunshade
if the following three conditions are met.
The outdoor unit is installed horizontally.
The ambient temperature exceeds 50°C.
The outdoor unit is directly exposed to sunlight.
If the previous three conditions are met but no sunshade is installed, the smart cooling product
will shut down because the components are applied beyond specifications.
Figure 7-17
Sunshade appearance