FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
9 Commissioning Core Components
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
74
DO Name
DO
Working
Type
Meaning
Parameter
19
Forcible alarm
enabling
The DO working type is independent of other parameters.
----End
9.1.1.3 (Optional) Commissioning the MDU
Prerequisites
The PDC has been powered on.
Control cables have been connected.
Preparations
Tool: multimeter
Documents: PDC user manual
Skill requirement: power distribution system engineer
Context
shows the front view of the MDU. The MDU allows you to set PDC parameters,
view the running status and alarms, and upgrade software.
Figure 9-1
MDU front view
(1) Alarm indicator