FusionModule1000A40 ICT Solution
Maintenance Guide
3 Routine Maintenance
Issue 01 (2019-03-05)
Copyright © Huawei Technologies Co., Ltd.
25
Device
Operation
Check Standard
Maintenance Guide
pipeline, and
nozzle.
All devices of the
fire extinguisher are
free from rust on the
exterior, and the
coating is intact.
Repaint.
The lead seal and
safety signs on
hand-operated
devices of the fire
cylinder are intact.
Replace the electrical actuator.
Check the pressure
pointer of the fire
cylinder.
The pressure pointer
is in the green zone.
Ask a fire engineer to check
whether the fire cylinder leaks
extinguishant. If leakage
occurs, the fire engineer
charges the extinguishant in
the local charging station.
Emergency
light
Disconnect the
power plug of the
emergency light.
The emergency light
turns on.
Replace by following
instructions in 4.4.2.11
Replacing an Emergency Light
(CE).
Smoke
detector
Check the smoke
detector indicator.
The indicator blinks
once every 6s.
Replace by following
instructions in 4.4.2.1
Replacing a Smoke Detector
(CE).
Heat
detector
Check the heat
detector indicator.
The indicator blinks
once every 6s.
Replace by following
instructions in 4.4.2.2
Replacing a Heat Detector
(CE).
3.5.6 Other Systems
Table 3-9
Monthly maintenance checklist for other systems
Item
Method
Check
Standard
Troubleshooting
Container
repainting
Check the
container exterior
for damage or
corrosion.
The container
and bases are
free from paint
flake-off, rust,
or corrosion.
Maintain or replace the rusty or
damaged part of the containers.
Repaint areas with paint flake-off or
rust by referring to 3.1 Container
Repainting.
External
environmen
t of
containers
Check whether
hazards or
potential hazards
exist around the
containers.
No hazard or
potential
hazard exists
around the
containers.
Take measures to handle potential
hazards.