FusionModule1000A20 CT Solution
Maintenance Guide
5 Parts Replacement
Issue 01 (2019-02-25)
Copyright © Huawei Technologies Co., Ltd.
89
Figure 5-19
Removing a point-type water sensor
Step 3
Install a new water sensor and tighten the screws.
The gap between the water sensor and the floor is 2 mm.
Step 4
Connect cables to the water sensor.
Step 5
Check that the new water sensor is working properly.
Drip a small amount of water onto the water sensor. If the monitoring software terminal generates an
alarm, the water sensor is working properly.
----End
Follow-up Procedure
Dispose of the removed water sensor that is confirmed faulty.
5.3.10 Replacing Access Control Components
5.3.10.1 Replacing an IC Card Reader
Prerequisites
An IC card reader needs to be replaced.
A spare IC card reader of the same model is available and functional.
Impact on the System
None
Preparations
Tools: Phillips screwdriver, protective gloves