FusionModule1000A40 Prefabricated All-in-One Data
Center
Installation Guide
8 Installing Devices Inside Pre-fab. Modules
Issue 03 (2020-06-09)
Copyright © Huawei Technologies Co., Ltd.
69
Figure 8-22
Positions of the threaded adapter and high-pressure hose
(1) Threaded adapter
(2) High-pressure hose
Step 5
(Optional) Install the electrical actuator.
Do not install the electrical actuator when installing the fire cylinder for the first time. Install the
electrical actuator when commissioning the fire extinguishing system.
1.
Verify that the electrical actuator ejector is reset. If the ejector is not reset, press down
the ejector, as shown by (1) in
ejector is pressed down.