Figure 5-76
Disconnecting the fire cylinder and fire extinguishing pipeline
2.
Remove the I-shaped connection pipe.
3.
Remove the threaded adapter from the container valve of the fire cylinder, as shown by
(2) in
Step 5
Remove the pressure operated switch hose from the container valve of the fire cylinder.
Step 6
Remove the screws securing the fire cylinder using a Phillips screwdriver, and remove the fire
cylinder fasteners.
Step 7
Remove the faulty fire cylinder from the installation position.
Step 8
Move the new fire cylinder to the installation position, and tighten the fire cylinder fasteners.
Keep the pressure gauge panel outwards so that people can view the reading.
Step 9
Connect the hose to the pressure operated switch.
Wrap the threads with sealing tape to ensure air tightness.
Step 10
Connect the fire cylinder to the fire extinguishing pipeline.