A.1.6.2 Installing Waterproof Metal Connectors
Prerequisites
●
Do not operate a feeder window outdoors under bad weather conditions if no
shelter is available.
●
Cables have been mounted on cable trays.
●
Cables need to be routed into a feeder window using waterproof metal
connectors.
Preparations
Tool: wrench dedicated for the feeder window
Materials: transparent sealant, sealing rubber strip
Skill requirement: skilled technician
Procedure
Step 1 Disassemble a waterproof metal connector using the dedicated feeder window
wrench shipped with the pre-fab. module, and take the plug out of the connector.
Figure A-10 Disassembling a waterproof metal connector
Step 2 Route a cable into the pre-fab. module through the waterproof metal connector.
NO TICE
● People inside and outside the pre-fab. module should work together to route
the armored power cable to the specified connection position inside the pre-
fab. module.
● To facilitate operation during internal routing, you can remove some top plate
in the pre-fab. module aisle.
FusionDC1000A Prefabricated All-in-One Data
Center
Installation Guide (IT Scenario)
A Basic Installation Operations
Issue 01 (2021-04-20)
Copyright © Huawei Technologies Co., Ltd.
114