4.1 Configurations of Upper-Level Circuit Breakers and
Power Cables
This section describes the recommended configurations of upper-level circuit breakers and
power cables for the BTS3900C. The recommended configurations are based on a fully
configured base station.
lists the recommended configurations of upper-level circuit breakers and power cables
for a BTS3900C AC cabinet.
Table 4-1
Recommended configurations of upper-level circuit breakers and power cables for a
BTS3900C AC cabinet
Input Power
Requirement for
the Circuit
Breakers on
Customer
Equipment
Cross-sectional
Area of an Input
Power Cable
Length of an Input
Power Cable
220 V AC single-
phase
16 A/1 P
(1)
4 mm
2
(0.025 in.
2
)
≤
15 m
110 V AC dual-live-
wire
20 A/2 P
NOTE
(1) P is short for Pole, indicating the number of switches simultaneously controlled by a pole.
lists the recommended configurations of upper-level circuit breakers and power cables
for a BTS3900C DC cabinet.
Table 4-2
Recommended configurations of upper-level circuit breakers and power cables for a
BTS3900C DC cabinet
Input Power
Requirement for
the Circuit
Breakers on
Customer
Equipment
Cross-sectional
Area of an Input
Power Cable
Length of an Input
Power Cable
-48 V DC
32 A/1 P
4 mm
2
(0.025 in.
2
)
≤
10 m
4.2 Power Distribution for the BTS3900C
This section describes power distribution schemes for BTS3900C cabinets when 110 V AC, 220
V AC, or -48 V DC power is supplied.
BTS3900C (Ver.C)
Hardware Description
4 BTS3900C Power System
Issue 03 (2013-05-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
95